Sansion Power Electric Co., Ltd.

Providing One-Stop Service For Customers

Manufacturer from China
Active Member
8 Years
Home / Products / SF6 Gas Analyzer /

Multi Function SF6 Gas Analyser Oil Degassing Dynamic Load Easy Operation

Contact Now
Sansion Power Electric Co., Ltd.
City:wuhan
Province/State:hubei
Country/Region:china
Contact Now

Multi Function SF6 Gas Analyser Oil Degassing Dynamic Load Easy Operation

Ask Latest Price
Video Channel
Brand Name :Sansion Power
Model Number :SXZD
Certification :ISO, SGS, ilac-MRA, CNAS
Place of Origin :Wuhan, China
MOQ :1 Set
Price :Negotiation
Payment Terms :T/T, L/C, Western Union
Supply Ability :100 Sets Per Month
Packaging Details :Carton / Plywood Case
Maxcapacity :<1000KN
Load Way :Electronic Load
Display :LCD
Loading Method :Dynamic Load
Control :Computer Control
Power Source :AC220V
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Automatic SF6 Gas Analyzer Oil Degassing Multi Function Shaker

General information

Multi-Function Shaker is applied for vibrate degassing of gases dissolved in oil ( gas chromatographic method), it is used in laboratory to heat, shake, degas various kinds of liquid under constant temperature and a fixed time. It is controlled by mico-computer to realize man-machine interaction.

Features

1. Large LCD screen, English interface.
2. Small size, light weight and low noise.
3. Easy operation, control temperature is accurate.

Specifications

1. Temperature measurement range: 0~120ºC


2. Temperature control range: Ambient temperature to 110ºC


3. Temperature control method: Digital PID auto control


4. Temperature control accuracy: Ambient temperature to 50ºC, ±0.2ºC
50ºC~100ºC,±0.3ºC
100~110ºC, ±0.5ºC


5. Shaking frequency: 275±3 times/minute

6. Shaking amplitude: 35mm

7. Quantity of samples: Injector 100ml *8pcs; conical flask 250ml *4pcs

8. Working modes:


1) Chromatography degassing: Constant temperature at 50ºC, shaking for 20 mins, static for 10 mins.


2) Water-soluble acid: Constant temperature at 75ºC, shaking for 5 mins, static for 0 minute.


3) User defined: Constant temperature 0 to 110ºC at any setting, shaking 0-99 mins at any setting

static 0~99 minutes at any setting.

4) Start and stop by hand


9. Voltage: AC220V±20%


10. Frequency: 50Hz±5%


11. Max. power consumption: 800W


12. Environment temperature: 10ºC-40ºC


13. Environment humidity: ≤85%


14. Oversize: 600×400×500


Warranty: One year quality guarantee after shipment.


More details please kindly contact with Sansion Power.Thank you!