Sansion Power Electric Co., Ltd.

Providing One-Stop Service For Customers

Manufacturer from China
Active Member
8 Years
Home / Products / Impulse Voltage Test System /

Customized Capacitance impulse current generator Power Testing System Long Life

Contact Now
Sansion Power Electric Co., Ltd.
City:wuhan
Province/State:hubei
Country/Region:china
Contact Now

Customized Capacitance impulse current generator Power Testing System Long Life

Ask Latest Price
Video Channel
Brand Name :Sansion Power
Model Number :SXCF
Certification :ISO, SGS, ilac-MRA, CNAS
Place of Origin :Wuhan, China
MOQ :1 Set
Price :Negotiation
Payment Terms :T/T, L/C, Western Union
Supply Ability :100 Sets Per Year
Delivery Time :15 Work Days
Packaging Details :Plywood Case
Display :LCD
Power Source :380V/220V110V at Cutomized
Each Stage :100kv 0.25UF or at Customized
Control :Computer Control
Nominal Voltage :200kv or at Customized
Impulse Capacitance :0.5UF or at Customized
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Automatic Impulse Voltage Test System Generator Power Testing System for Lighting Test

System instruction Main Parameters for System

  • Nominal voltage: ±200kV 
  • Rated stage voltage: ±100kV
  • Rated energy: 10kJ
  • Impulse capacitance: 0.5µF
  • Number of stages: 2
  • Rated stage capacitance: 1µF(each impulse capacitor 1µF at 100kV, total 2pcs)
  • Impulse voltage waveform: generated when load capacitance is 300-3000pF.

T1=1.2µs±30%, T2=50µs±20%, standard lightning impulse voltage full waveform of peak voltage deviation≤3%;


Standard operation waveform 250±20%/2500±60%. These 2 Impulse voltage waveform parameters and error are accorded with national requirements of IEC standard.

  • Voltage utilization factor: Standard lightning impulse voltage waveform ≥90% when load capacitance is below 1000pF, standard operation impulse voltage waveform≥80% when load capacitance is below 2000pF. Standard operation impulse voltage waveform ≥70%.
  • Locking range: level voltage is within the range of 20%-100% rated voltage, positive and negative locking range no less than 25%.
  • Out-of-control rate of synchronous discharge: <5%
  • Min. output voltage: ≥±20% of rated voltage.
  • Instability of discharge voltage: <±1.0%
  • Continuous time: Above 2/3 of rated voltage, continuous working when charge and discharge once every 120s. Below 2/3 of rated voltage, continuous working when charge and discharge once every 60s.